IInntteelllliissDDeevviicceeNNeett NNeettwwoorrkk MMoonniittoorr MMooddeellss 77660044,, 77664444 && 77667799 Installation and Operati
1.5.2 DeviceNet Features Table 5 DeviceNet Features Device Type Generic Explicit Peer to Peer Messaging No I/O Peer to Peer Messaging No Configur
2 Installation Instructions Mounting 2-2 Pneumatic Connections 2-3 Tubing and Fittings 2-3 Porting 2-4 Maintenance 2-4 Switch Adjustment 2-5 W
IMPORTANT: If the valve monitor is already in the field mounted on an actuator and valve, please follow the field wiring instructions in Section 2.
Figure 3 2.2 Pneumatic Connections Personal injury and/or property damage may occur from loss of process control if the supply medium is not c
2. Apply sealant/lubricant or Teflon tape to the male pipe threads. With any sealant tape, the first one or two threads should be left uncovered to
2.3 Switch Adjustment Switches are factory set. If you need to adjust switches for any reason follow instructions below. For steps 1-8 refer to F
2.4 Wiring Instructions All wiring must be in accordance with National Electrical Code (ANSI-NFPA-70) for the appropriate area classifications.
Tech-309 2-7
2.4.1 DPAC Connector Pin-out Diagrams Tech-309 2-8
2.5 DeviceNet Cabling Information Correct termination of the trunk and total trunk and drop limits for the baud rate the network is to run at mus
Revision History Revision 1.0 1 June, 2004 Initial Version Revision 1.1 10 February, 2005 Document was updated to reflect new PCB design, additio
3 DPAC Configuration Communication Settings 3-2 Baud Rate and Address via the DIP Switch 3-2 Baud Rate and Address via the Bus 3-4 Tech-309 3-1
3.1 Communication Settings For the appropriate DIP switch settings for the address and baud rate of the DPAC refer to Figure 15 and Tables 9 and 10.
Table 10-a Switch S1 MAC ID Returned Value SW6 SW5 SW4 SW3 SW2 SW1 OFF OFF OFF OFF OFF OFF 0 0x00 OFF OFF OFF OFF OFF ON 1 0x01 OFF OFF OFF OFF
Table 10-b Switch S1 MAC ID Returned Value SW6 SW5 SW4 SW3 SW2 SW1 ON OFF ON ON OFF ON 45 0x2D ON OFF ON ON ON OFF 46 0x2E ON OFF ON ON ON ON 47
Appendix A Contact Information USA Westlock Controls Corp. 280 Midland Ave. Saddle Brook, NJ 07663 Phone: (201) 794-7650 • Fax: (201) 794-0913 Emai
Tech-309 - 1 - Appendix B Westlock Controls Corporation DeviceNet DN-WLCIO Device Specifications Publication # 07241992 Date 10/09/200
Tech-309 - 2 - Device Profile The DN-WLCIO is the General Purpose Discrete I/O Device (Profile Number 7) Objects Present in Device Object name
Tech-309 - 3 - Identity Object Class Code: 01(0x01) Identity Object Class Attributes Class=1, Instance=0, Attribute=1,
Tech-309 - 4 - Message Router Object Class Code: 02(0x02) Message Router Object Class Attributes Class Implementation is based
Tech-309 - 5 - DeviceNet Object Class Code: 03(0x03) DeviceNet Object Class Attributes Class=3, Instance=0, Attribute=1Attribute ID Ac
1 Introduction Scope of Manual 1-2 Symbols Used in this Document 1-2 About DeviceNet 1-2 Westlock Intellis DeviceNet Module EL-40092 1-3 Modul
Tech-309 - 6 - ** Baud Rate is settable through DeviceNet only if switch S1 positions 7 and 8 are both in the ON position. See Table below.
Tech-309 - 7 - Assembly Object Class Code: 04(0x04) Assembly Object Class Attributes Implementation is based on the Static As
Tech-309 - 8 - Assembly Object Instance #4 Attributes (Instance #4 is type: 8 point with No Status Bit) Class=4, Instance=4, Attribute=
Tech-309 - 9 - Assembly Object Instance #32 Attributes (Instance #32 is type: 2-Point Output, and is used only when the device has 2 outputs or
Tech-309 - 10 - Assembly Object Instance #33 Attributes (Instance #33 is type: 4-Point Output, and is used only when the device has 4 outputs.
Tech-309 - 11 - Connection Object Class Code: 05(0x05) Connection Object Class Attributes Implementation is based on revision 0
Tech-309 - 12 - Connection Object Instance #1 Attributes (Explicit Message Connection – Instance #1) Class=5, Instance=1, Attribut
Tech-309 - 13 - Connection Object Instance #2 Attributes (Poll I/O connection - Instance #2) Class=5, Instance=2, Attribut
Tech-309 - 14 - Discrete Input Point Object Class Code: 08(0x08) Discrete Input Point Object Class Attributes Class=8, Instance=0, Attri
Tech-309 - 15 - Discrete Output Point Object Class Code: 09(0x0A) Discrete Output Point Object Class Attributes Class=9, Instanc
1.1 Scope of Manual This manual contains installation, configuration and specification data for the DPAC DeviceNet valve controller. This manual a
design and implement, DeviceNet has the capability to interconnect complex as well as simple devices to the same network, easily accommodating both a
1.4.1 Module Bit Map Table 1 I/O TYPE MODULE REFERENCE BITMAP OF DATA INSTANCE #4 (8-POINT INPUT WITH NO STATUS) ATTRIBUTE #3 (DATA) INPUT 0 Hall
Table 2 Value Meaning 1 Auto Delete: The Connection Class automatically deletes the Connection if it experiences an IWT timeout. This is the default
Table 3 Module p/n LED State Indicates Off There is no power applied to the device. Green Device is operating in a normal condition. Flashing Gre
1.4.4 Module Layout J1 Figure 1- EL-40092 1.5 Device Specifications 1.5.1 Specifications Table 4 Round Physical Media Shielded 2 twisted pairs f